- Products
- Manufacturers
- Advanced Energy
- AET
- Amphenol
- Apollo Solar
- Astronergy
- BenQ Solar
- Blue Sea Systems
- Blue Sky Energy
- Bogart Engineering
- Canadian Solar
- Chint Power
- CivicSolar
- Concorde Battery Corp
- Conergy
- Cooper Bussmann
- Cooper B-Line
- DIEHL
- DPW Solar
- DECK
- Delta Lightning Arrestors
- Deltec Company
- ET Solar
- Ecolibrium Solar
- Ecofasten Solar
- Ejot Fasteners
- Enphase Energy
- Fronius
- Fullriver DC Battery
- Hanwha SolarOne
- Huber Suhner
- IOTA Engineering
- Interstate Batteries
- Ironridge
- ISOFOTON
- Kaco
- Kipp and Zonen
- Kyocera
- LG
- Littelfuse
- Locus Energy
- MK/ Deka Batteries
- Magnum Energy
- Meca Solar
- Mersen (Ferraz Shawmut)
- MidNite Solar
- Morningstar
- Multi-Contact (MC)
- NOV Monoflo
- OutBack
- P3 International
- PV Powered
- PanelClaw
- Perlight Solar
- Phocos
- Power-One
- ProSolar
- Quick Mount PV
- REC
- ReneSola
- Rennsteig Tools Inc.
- Rogue Engineering
- S-5!
- SMA
- Samlex America
- Sanyo
- Sharp
- Shurflo
- Siemens
- Soladeck
- Solar Converters Inc.
- Solar Pathfinder
- SolarBOS
- SolarEdge
- SolarMax
- SolarWorld
- Solectria
- Solmetric
- Sonnen Systems
- Specialty Concepts
- Square D
- Steca
- SunPumps
- Suniva
- Sunlink
- Surrette Battery Company
- Thompson Technology
- Tigo Energy
- Trina Solar
- Trojan Battery Company
- Tyco Electronics
- Unirac
- Wattsun
- Wiley Electronics
- Xantrex
- Xunlight
- Yingli Solar
- Zomeworks
- Solar Panels
- Inverters
- Racking & Mounting
- Batteries
- Charge Controllers
- Monitoring
- Installation Supplies
- Manufacturers
- Installers
- Projects
- Tech Help
- About Us
Tech Help
Got a question? Take advantage of the knowledge and expertise of other CivicSolar members. Have a special skill or tip to pass on? Consider posting an article and adding to the depth of the CivicSolar knowledge base.
-
The use of nasty in roof
Added by Roofing Dublin on 12 hours ago
The use of nasty in roof structure has significantly increased over the last few decades because of obvious and significant benefits when compared to other types of roof
Comment
-
Can a Midnite Solar Classic 200 communicate with an Outback Power system through the Outback Mate?
Asked 1 day ago
Or do you need an Outback Flexmax charge controller for that capability?
Question
-
Larry,If you are using
Answered by SF_Solar on 1 day ago
Larry, If you are using Enphase M215 at 240Vac, then you would need 5 two-pole breakers at 20A each. For 100A of solar back feed, you may need a line-side tap.
Answer
-
I Have 2 2000 w inverters at
Answered by jimpoe63 on 2 days ago
I Have 2 2000 w inverters at 110v ea, I need 220v to run some of my appliances, (iwant to go off grid) what else do I need ( AC, stove dryer etc.) thanks jimpoe
Answer
-
I have 70 ac microinverter panels, I'm going to mount landscape on my barn roof. What size service panel, breakers, and wires do I need?
Asked 3 days ago
I have 70 ac microinverter panels I'm going to mount on my barn roof landscape.
Question – 1 comment
-
You should contact your
Answered by mckensie on 3 days ago
You should contact your utility before attempting any grid connection. Also consult with a qualified electrician.
Answer
-
You have a few options:Basic
Answered by SF_Solar on 3 days ago
You have a few options: Basic wire nut or terminal splices inside.
Answer
-
What happens if you
Answered by SF_Solar on 3 days ago
What happens if you disconnect your solar panel at night? Could there be a bright street light or other light hitting the PV panel?
Answer
-
Could it be looking for solar
Answered by SF_Solar on 3 days ago
Could it be looking for solar panels? A web search indicates that Error E06 means "Missing PV Panels". Link: http://goo.gl/cXljk
Answer
-
It may not be an issue since
Answered by SF_Solar on 3 days ago
It may not be an issue since normal conditions will produce something in the range of 180W per module. See the CS250 module data, below as an example.
Answer
-
Removing and replacing the
Answered by SF_Solar on 3 days ago
Removing and replacing the meter only turns the power off and then back on again.
Answer
-
UL 1741, which all US grid
Answered by mhamon on 3 days ago
UL 1741, which all US grid tied inverters are listed to, requires that the inverter disconnect from the grid when the grid voltage or frequency goes outside of a specifie
Answer
-
It depends. You are going to
Answered by mhamon on 3 days ago
It depends. You are going to lose output based on how different the I-V curves are for the different modules.
Answer
-
You should have your
Answered by mhamon on 3 days ago
You should have your installer come out and check the system out. The meter swap should not have effected the inverter operation.
Answer
-
Am adding 6 to the current
Answered by Ronald on 4 days ago
Am adding 6 to the current 8 panels all are 60 cell 210 watt panels
Answer
-
I suggest that you combine
Answered by SF_Solar on 4 days ago
I suggest that you combine them in a small breaker panel. How many of the M190s do you have now?
Answer
-
Defining US Content Compliancies: ARRA vs BAA vs TAA vs Made in USA vs Ex-Im
Added by nicholasyeh on 4 days ago
As the solar photovoltaic industry continues to grow in the United States, installers and project developers will have to become more
Article
-
How do you splice a M215 trunk line to an M190 trunk cable, as I am adding a new M215 - 6 panel array to an existing M190 array?
-
PG&E installed a smartmeter. they suggested that i check my systems inverter to ensure it turned back on
Asked 5 days ago
I'm not sure solar panel inverter turned back on after PG&E shut off power there's words like sync ac and state 104 in the m
Question – 2 comments
-
Can horizontal single axis
Added by enorbutter on 05/17/2013
Can horizontal single axis trackers like http://www.scorpiustrackers.com/products.html help to improve it?
Comment
-
Can I mix panel manufacturers, Canadian w/ REC scm 225?
Asked 05/14/2013
Can I mix panel manufacturers, Canadian w/ REC scm 225? discussion,solar installation discussion,solar forum
Question – 1 comment
-
Connecting more wattage than recommended on Phocos MPPT Controller...
Asked 05/14/2013
I have a Phocos 30A 24V Mppt controller. The max PVwatt recommended is 900W . However I have 4 x 250watts panels.
Question – 1 comment
-
There is correspondence on
Answered by SF_Solar on 05/13/2013
There is correspondence on the web indicating that this can be done (see below).
Answer
-
All you need to do this is to
Answered by solarmanjack on 05/07/2013
All you need to do this is to make sure your inverter is a grid tie inverter.
Answer
-
Grid tie inverters are
Answered by solarmanjack on 05/07/2013
Grid tie inverters are islanding inverters. Before they can produce power they read the voltage of the grid.
Answer